FE-INDUSTRIAL thyristor-based UPS 10-800 KVA

Features:

  • True Online technology: Load is supplied with power without interruption regardless of the UPS operating mode, transfer between UPS modes without interruption
  • High output power: This industrial family provides 0.9 output P.F.
  • Full DSP control: Full DSP Control avoids the risks caused by analog devices failure and makes the control system more stable and reliable
  • Wide input voltage: The range of AC input voltage is (380Vac I 400Vac I 415Vac) (-25% / +20%), minimizing the chance of transferring to battery mode, thereby allowing battery to serve longer life. Wide input frequency ranging from 45Hz to 65Hz.
  • Intelligent battery management: Intelligent battery management system and advanced battery auto float/boost charge technology, reduces the frequency of battery maintenance, greatly improves the battery efficiency, and extends battery life.
  • Battery discharge time prediction: the system will display the backup time of battery calculated based on discharge current and voltage.
  • Battery self-test: battery is automatically tested at regular intervals.
  • Flexible battery arrangements: Flexible battery configuration ranging from 360-408Vdc / 480Vdc.
  • N+X parallel redundant: N+X parallel redundant design, up to 6 units available, makes the configuration more flexible and reliable. In case of parallel unit failure, the failed unit will disconnect from load, other units will keep supplying power to load based on equal sharing without interruption of supply. It is easy to configure the parallel system just by connecting the parallel cables and doing corresponding settings. Non-fixed Master-Slave relationship: Among several UPS in parallel, the unit startup first is Master UPS, the others are Slave. The master and slave may be exchanged. ·
  • Strong overload capability:
    • 110% overload for 60 minutes.
    • 125% overload for 10 minutes
    • 150% overload for 1 minute.
  • Power walk-in: Specially designed power walk in function, in which rectifier of each unit in parallel system will be turned on in sequence at intervals to avoid the sudden load impact on the generator, thereby reducing the capacity oversizing of the generator required.
  • LBS synchronization: Synchronizing the output of the two independent UPS systems (single unit or parallel) even when the two systems are operating on different modes (bypass/inverter) or on battery is possible with this UPS.
  • Multi-protection: Self-diagnosis will take place before start-up for safety and machine protection. Multi-protection: AC input under/over voltage, overload, short-circuit, over-current, over bus voltage, over-temperature, fan failure, auxiliary power failure, battery under voltage, battery over-charge and so on.
  • EPO function: A concave red EPO button with transparent cover is embedded in the LCD control panel for emergency power off.
  • User-friendly network management: English/French LCD and LED mimic diagram: real time operation parameters and status, RS232 & RS485 communication ports: for local monitor with corresponding software, and MODBUS protocol is optional. SNMP adapter (optional): for remote monitor through network
  • Dry contacts for additional monitoring:
    • UPS on Inverter
    • Mains input failure
    • Remote EPO
    • Battery low voltage alarm (optional)
    • UPS fault
    • UPS alarm
    • UPS on battery
    • UPS on bypass (optional)